Alarm color and blink conventions (SCADA-008)¶
The alarm objects follow the alarm-state model of ANSI/ISA-18.2 and IEC 62682 (Management of alarm systems for the process industries). The colors also follow common ISA-101 HMI practice. These standards do not require specific colors. They ask for colors that are consistent, reserved for alarms, and backed up by non-color cues (text, shape). This library follows that approach. The defaults below are CSS custom properties, so you can adapt them to your site's HMI philosophy.
States (AlarmIndicator.value)¶
| State | Meaning | Visual | Blink |
|---|---|---|---|
normal |
condition inactive, nothing to acknowledge | grey shape, text NORMAL |
none |
active_unacknowledged |
condition active, operator not yet acknowledged | shape filled with the priority color, thick border in the priority color, text ACTIVE · UNACK, ACK button |
fast (0.8 s period) |
active_acknowledged |
condition active, acknowledged | shape filled with the priority color, text ACTIVE · ACK |
none (steady) |
cleared_unacknowledged |
condition returned to normal before acknowledgement | shape outlined in the priority color, text CLEARED · UNACK, ACK button |
slow (2 s period) |
Transitions: activate() (normal/cleared → active unack), clear() (active
unack → cleared unack, active ack → normal) and acknowledge() (active unack →
active ack, cleared unack → normal). An acknowledgement from the front end
calls the on_acknowledge callbacks with the alarm_id (SCADA-007).
Priorities (AlarmIndicator.priority)¶
| Priority | Label | Default color (--awi-prio-*) |
Redundant shape |
|---|---|---|---|
critical |
P1 | red #d10000 |
diamond |
high |
P2 | orange #f27b00 |
triangle |
medium |
P3 | yellow #e6c700 |
square |
low |
P4 | cyan #00a4c7 |
circle |
Numeric alarm levels (alarm_level)¶
| Level | Default color | Text badge |
|---|---|---|
lo, hi |
amber (--awi-alarm-lo, --awi-alarm-hi) |
LO, HI |
lolo, hihi |
red, bold (--awi-alarm-lolo, --awi-alarm-hihi) |
LOLO, HIHI |
With deadband, the level doesn't drop back until the value has moved back
past the limit by at least the deadband (ALARM-003).
Reduced motion (A11Y-005)¶
When the user agent requests reduced motion (prefers-reduced-motion: reduce),
blinking is turned off. Instead, the alarm shapes (and blinking LEDs) get a
steady dashed outline, so an unacknowledged alarm still looks different from an